High Voltage Shunt Capacitor is reactive power compensation unit of simple,economic and reliable,which can improve power grid PF,decrease of voltage loss and loss and improve power distribution ability.
Feature:
low loss of medium
high level of explosion-proof enclosures
Insulating oil meets environmental requirements
The capacitance value varies little with temperature;
Withstand fault current under 10kA
Built-in discharge resistor, when removed from the power supply, the capacitor can make the remaining voltage within 5 minutes from the UN under 50V
Usage Condition
Altitude: not more than 1000m
Ambient Temperature: (- 40 ~ +50) ºC;
Non-corrosive gas and steam, no conductive or explosive dust; no violent vibration;
Three phase High Voltage Shunt&Filter Capacitor
Implementation standard:
IEC60871: 1997 "Nominal voltage above 1kV shunt capacitor for AC power system "
IEC 61642: 1997 "Application of Filters and Shunt Capacitors in Industrial Communication Networks Affected by Harmonics"
Feature:
low loss of medium
high level of explosion-proof enclosures
Insulating oil meets environmental requirements
The capacitance value varies little with temperature;
Withstand fault current under 10kA
Built-in discharge resistor, when removed from the power supply, the capacitor can make the remaining voltage within 5 minutes from the UN under 50V
Usage Condition
Altitude: not more than 1000m
Ambient Temperature: (- 40 ~ +50) ºC;
Non-corrosive gas and steam, no conductive or explosive dust; no violent vibration;
Three phase High Voltage Shunt&Filter Capacitor
Model | (kV) Rated Voltage | (kvar) Rated Capacity | (mm) Size | (kg) Weight | DWG | |||||||
A | B | C | D | E | F | G | H | |||||
SKD5-066-100I | 6.6 | 100 | 420 | 120 | 470 | 504 | 350 | 150 | 140 | 562 | 28 | DWG 1 |
SKD5-066-150I | 6.6 | 150 | 420 | 120 | 470 | 504 | 435 | 150 | 200 | 647 | 34 | |
SKD5-066-200I | 6.6 | 200 | 620 | 140 | 670 | 704 | 365 | 250 | 140 | 632 | 47 | |
SKD5-066-250I | 6.6 | 250 | 620 | 160 | 670 | 704 | 365 | 250 | 140 | 632 | 52 | |
SKD5-066-300I | 6.6 | 300 | 620 | 155 | 670 | 704 | 435 | 250 | 200 | 702 | 60 | |
SKD5-110-100I | 11 | 100 | 460 | 110 | 510 | 544 | 365 | 175 | 140 | 577 | 30 | |
SKD5-110-150I | 11 | 150 | 460 | 140 | 510 | 544 | 365 | 175 | 140 | 577 | 35 | |
SKD5-110-200I | 11 | 200 | 620 | 140 | 670 | 704 | 365 | 250 | 140 | 632 | 47 | |
SKD5-110-250I | 11 | 250 | 620 | 160 | 670 | 704 | 365 | 250 | 140 | 632 | 52 | |
SKD5-110-300I | 11 | 300 | 620 | 155 | 670 | 704 | 435 | 250 | 200 | 702 | 60 | DWG 1 |
SKD5-110-350I | 11 | 350 | 620 | 180 | 670 | 704 | 435 | 250 | 200 | 702 | 69 | |
SKD5-110-450I | 11 | 450 | 620 | 190 | 670 | 704 | 595 | 250 | 200 | 807 | 98 | |
SKD5-120-100I | 12 | 100 | 460 | 110 | 510 | 544 | 365 | 175 | 140 | 577 | 30 | |
SKD5-120-150I | 12 | 150 | 460 | 140 | 510 | 544 | 365 | 175 | 140 | 577 | 36 | |
SKD5-120-200I | 12 | 200 | 620 | 135 | 670 | 704 | 365 | 250 | 140 | 632 | 46 | |
SKD5-120-250I | 12 | 250 | 620 | 160 | 670 | 704 | 435 | 250 | 140 | 632 | 52 | |
SKD5-120-300I | 12 | 300 | 620 | 155 | 670 | 704 | 435 | 250 | 200 | 702 | 60 |
Implementation standard:
IEC60871: 1997 "Nominal voltage above 1kV shunt capacitor for AC power system "
IEC 61642: 1997 "Application of Filters and Shunt Capacitors in Industrial Communication Networks Affected by Harmonics"