Harmonic filtering function: can filter 2-51 times harmonic in the same time, efficiency up to 97%;Reactive compensation function:1) constant reactive power mode;2) constant power factor mode;Unbalance compensation:Balance the three-phase current of the system to avoid single-phase overload of the transformer and impro

Featured Products

APF AHF SVG 380V 400V 50Hz 3Phase 4Line Active Power Harmonic Filter
  • Harmonic filtering function: can filter 2-51 times harmonic in the same time, efficiency up to 97%;
  • Reactive compensation function:1) constant reactive power mode;2) constant power factor mode;
  • Unbalance compensation:Balance the three-phase current of the system to avoid single-phase overload of the transformer and improve the effective use capacity;
  • Other basic functions:The CT can be installed on the load side or the grid side according to the user's choice. The device can be automatically compatible with the CT phase sequence.
APF AHF SVG 380V 400V 50Hz 3Phase 4Line Active Power Harmonic Filter
Before APF is running, THDI is 26%:                                                                  After APF is power on, THDI was dropped to 6%:
        APF AHF SVG 380V 400V 50Hz 3Phase 4Line Active Power Harmonic Filter                 APF AHF SVG 380V 400V 50Hz 3Phase 4Line Active Power Harmonic Filter

APF AHF SVG 380V 400V 50Hz 3Phase 4Line Active Power Harmonic Filter
                                             APF AHF SVG 380V 400V 50Hz 3Phase 4Line Active Power Harmonic FilterAPF AHF SVG 380V 400V 50Hz 3Phase 4Line Active Power Harmonic Filter
Rated compensation conventional capacity50A80A100A120A150A200A
Rated overload capacity1.2 times rated current /1 min, 2.5 times rated current /10ms
Wiring modeThree-phase four-wire system (three-phase three-wire system can be customized) under AC380V Voltage class Three-phase three-wire system under AC690V Voltage class
Cooling methodAir cooling
Ambient temperature40°C , up to 55°C , 2%/K over-temperature automatic derating
Parallel operationSupport multi-machine parallel connection, can not equal capacity parallel
Communications protocolRS-485, Modbus-RTU communication protocol
Rated operating voltageAC380V±20%AC690V±15%
Air cooling requirements (full load)330m3/h600m3/h1000m3/h1200m3/h1200m3/h1000m3/h
Noise level  60dB 65dB
Harmonic filtering range2-51 times
Function setCombination of harmonic compensation, reactive compensation, unbalance compensation and free compensation with priority
Dry contactOne input contact: control switch machine; three output contacts: running power failure
Altitude 3000 m
Voltage classAC380V±20%,AC690V±20%
Rated operating frequency50Hz±5%
Response time< 5ms
Transformer installation locationPower side / load side
Dimension(mm) Wallmount400x190x570450 x 200 x 620480 x 270 x 707 
(width x depth x height) Drawer530x550x190530 x 550x190475 x 600 x 270550x600x270
Weight (kg)25 kg35 kg 70 kg70 kg62 kg
Protection class                                                                                                                                                                Standard IP20
CertificationType test report of National Electronic Control and Distribution Equipment Quality Supervision Center, China Taier  Laboratory Inspection Report

APF AHF SVG 380V 400V 50Hz 3Phase 4Line Active Power Harmonic Filter