10/15/20kva 380VAC input to 380VAC input low frequency transformer UPS
Product Description
Low Frequency Online UPS GP9110C 6kVA to 15kVA
Key features:
1. 1ph/1ph or 3ph/1ph, support 380/400/415V, 50/60Hz power system.
2. Pure-online double conversion technology, to provide the best quality of power supply.
3. Suitable for all kinds of loads, and a high overload capacity.
4. Super wide range of input voltage anti-interferance,adapt to harsh environment in power network.
5. Intelligent battery management, extending the battery life.
6. Large LCD display in Chinese and English, and Friendly human-machine interface.
High reliability design:
1. Double-conversion online design, make the output for UPS frequency tracking, phase-locked regulator, filter noise,low distortion, without interference of pure sine wave power supply, so that UPS for use provide more comprehensive and perfect protection.
2. Output conversion time, is zero to meet the sophisticated equipment for power high-standard requirements.
Technical Specifications of OEM UPS GP9110C GP9310C Series
Product Description
Low Frequency Online UPS GP9110C 6kVA to 15kVA
Key features:
1. 1ph/1ph or 3ph/1ph, support 380/400/415V, 50/60Hz power system.
2. Pure-online double conversion technology, to provide the best quality of power supply.
3. Suitable for all kinds of loads, and a high overload capacity.
4. Super wide range of input voltage anti-interferance,adapt to harsh environment in power network.
5. Intelligent battery management, extending the battery life.
6. Large LCD display in Chinese and English, and Friendly human-machine interface.
High reliability design:
1. Double-conversion online design, make the output for UPS frequency tracking, phase-locked regulator, filter noise,low distortion, without interference of pure sine wave power supply, so that UPS for use provide more comprehensive and perfect protection.
2. Output conversion time, is zero to meet the sophisticated equipment for power high-standard requirements.
Technical Specifications of OEM UPS GP9110C GP9310C Series
Model | GP911C 6-15KVA | GP9311C 10-40KVA | ||||||||
6KVA | 8KVA | 10KVA | 15KVA | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | ||
Capacity | 6KVA/4.8KW | 8KVA/6.4KW | 10KVA/8KW | 15KVA/12KW | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | |
Rated voltage | 220V single phase | 380V three phase 4 wires+G | ||||||||
Rated frequency | 50/60HZ | |||||||||
AC input | ||||||||||
Voltage range | 220V±25% single phase | 380V±25% three phase 4 wires+G | ||||||||
Frequency range | 50/60HZ±5% | |||||||||
Soft strat | 0-100% 5sec | |||||||||
Power factor | >0.92(with input filter) | |||||||||
Bypass input | ||||||||||
Voltage range | 220V±25% singke phase | 380V±25% three phase 4 wires+G | ||||||||
Frequency range | 50/60HZ±10% | |||||||||
Inverter bypass | (overload)0ms | |||||||||
Output | ||||||||||
Voltage accuracy | 220V±1%(steady-state load),220V±3%(load fluctuations) | |||||||||
Frequency accuracy | 50/60Hz±0.05Hz(battery power) | |||||||||
Power factor | 0.8(lagging) | |||||||||
Distortion | <3%(linear load), <5%(non linear load) | |||||||||
Steady-state response time | <10ms | |||||||||
Overload capacity | 110%load can run normally 125%10min 150%1min | |||||||||
battery | ||||||||||
Nominal voltage | 192V | 360V | ||||||||
Float voltage | 216V | 405V | ||||||||
Cut-off voltage | 168V | 315V | ||||||||
Charger current | 1A-50A(According to the battery capacity can be set configuration) | |||||||||
Other | ||||||||||
Display | LED\LCD | |||||||||
Alarm | Sound and light alarm | |||||||||
Protection | UPS over current,short circuit,under voltage,over temperature | |||||||||
Environment | ||||||||||
Noise | 60-65dB | |||||||||
Operating | Temperature0-40°C Relative humidity 0-90% | |||||||||
Box color | Gray (optional) | |||||||||
Physical | ||||||||||
Wight (KG) | Net | 122 | 125 | 143 | 175 | 182.5 | 235.5 | 285.5 | 354.8 | 354.8 |
Gross | 142 | 147 | 163 | 199 | 225.5 | 268.5 | 325.2 | 389.5 | 389.5 | |
Dimesions W×D×H(mm) | 210×600×560 | 305×586×850 | 350×675×920 | 430×792×1060 |